Your SICK ID gives you access to our extensive range of services. This includes direct online orders, price and availability checks, and access to our digital services.
To read the details (Event Qualifier, Event Code) there is CIP object which offers access to all information.
Details are found in the attached document (IO-Link CIP Integration-v58.pdf), chapter 8. To get the event details the CIP explicit messaging system needs to be used.
The easiest access offers attribute 22.
The response of the explicit message is the oldest pending event at the respective port. Reading the event automatically deletes this event from the queue in the IO-Link master. As soon as all pending events have been read / have been deleted the "Event Flag" in the Ethernet/IP process data is erased.